- Rating: 3.0Amp - 50.0Amp
- Input power: 125/250Vac, 50Vdc,
50/60Hz
- Interrupt capacity: 1000Amp, 125Vac; 200Amp,
250Vac
- Dielectric strength: 1500Vac, 1
minute
- Resettable overload capacity: 10 times rated
current
- Voltage drop: less than 0.25V
- Insulation resistance: 500 M. ohms
- Reset time: within 60 seconds
|
- Temperature rise: less than 65 degrees in
Celsius, at 100% of rated current applied continuously at 25 degree in
Celsius
- Calibration (at 25 degree)
100% of rated current: hold, no-trip 135%
of rated current: trip in 1 hour 200% of rated current: within 40
seconds trip 300% od rated current: within 10 seconds
trip |