- Rating: 1.0Amp - 10.0Amp
- Input power: 125/250Vac, 50Vdc,
50/60Hz
- Interrupt capacity: 1000Amp, 125Vac; 200Amp,
250Vac
- Dielectric strength: 1500Vac, 1
minute
- Resettable overload capacity: 6 times rated
current
- Voltage drop: less than 0.25V
- Insulation resistance: 500 M. ohms
min.
- Push to reset ( within 20 seconds)
|
- Temperature rise: less than 65 degrees in
Celsius, at 100% of rated current applied continuously at 25 degree in
Celsius
- Endurance: 500 cycles min. at 150% rated
current, 125Vac
- Calibration (at 25 degree)
100% of rated current: hold, no-trip 135%
of rated current: trip in 1 hour 200% of rated current: 3-30 seconds
trip 300% od rated current: 0.5-4.0 seconds
trip |